AIS switch cabinet, Rmu, 24kv switch

Combining with advanced technology both at home and abroad, we developed GSM series indoorair insulated (modular SF6) switchgear (hereinafter referred to as switchgear) and GSC series (SIC and SQC type) indoor SF6 load break switch and  composite apparatus.   It meets IEC298, IEC60420, IEC60265, GB 3906, GB38

Featured Products

Combining with advanced technology both at home and abroad, we developed GSM series indoorair insulated (modular SF6) switchgear (hereinafter referred to as switchgear) and GSC series (SIC and SQC type) indoor SF6 load break switch and  composite apparatus.  
 It meets IEC298, IEC60420, IEC60265, GB 3906, GB3804, GB16926 standards. The switchgear has reliable fault operation prevention function.
AIS Switchgear, Rmu, 24kv SwitchAIS Switchgear, Rmu, 24kv SwitchAIS Switchgear, Rmu, 24kv SwitchAIS Switchgear, Rmu, 24kv SwitchFeatures
SF6 gas is adopted as insulating and arcing medium. The arcing mode is constant magnetic field rotating arc, so its arcing ability will not be affected by magnitude of arc and current. Besides, it has good breaking capacity, small over-voltage, long electrical life and maintenance-free arc extinguish chamber. -Advanced GSC series (SIC and SQC type) indoor SF6 load break switch and composite apparatus are adopted. It has three positions:"closed", "open", "earthed".
Specification: 

Item

Unit

Parameters

Rated voltage

KV

12

24

Rated frequency

Hz

50

Rated current

A

630/1250

Rated load breaking current

A

630

Rated short time withstand current (effective value)

A

20/31.5

Rated short circuit duration

S

3

Rated short circuit making current

KA

50

Rated peak withstand current

KA

50

Rated cable charging breaking current

A

10

Rated active load and close circuit breaking current

A

630

MAX transfer current

A

1750

Earthing switch short time withstand current (2s)

KA

17.4/20

Rated current breaking times

Times

≥10

Load break switch mechanical life

Times

≥5000

Earthing switch mechanical life

Times

≥2000

1 min power frequency withstand voltage

Common value

KV

42

55

Across insulate distance

KV

48

65

Lightning impulse withstand voltage

Common value

KV

75

125/150

Across insulate distance

KV

85

150/160

Operating mechanism

 

Manual or motor

Operating voltage

V

AC/DC 220/110,

DC48/24

Protection degree

 

IP3X

AIS Switchgear, Rmu, 24kv SwitchAIS Switchgear, Rmu, 24kv Switch
 

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours