YB series prefabricated substations used for AC 50Hz and 60Hz, high voltage side rated voltage 3.6~40.5kV, low voltage side rated voltage 220~690V, rated capacity 2000kVA and below system. It can be used as a permanent power supply device and as a temporary power supply for construction sites. It is a pre-installed substation with outdoor use conditions accessible to the public, which can replace civil substations.
1. Small volume, cover a small area, compact structure, easy to move.
2. Simple installation, quick power supply, simple maintenance, no person on duty.
3. The box body adopts a good heat insulation and ventilation structure, beautiful and generous appearance, good heat insulation performance, and the box body is equipped with upper and lower ventilation devices. Can be equipped with forced air cooling device and automatic temperature control device, which can automatically control the temperature of the transformer, ensure the transformer to operate at full load.
4. Each independent unit can be equipped with perfect control, protection device and lighting system.
5. Safety isolation net door is set in the transformer room. Interlock device is installed on the net door to prevent entering and ensure safety.
Low voltage side:
The low-voltage main incoming line switches can choose CW1, HSW1, RMW1, SW1 and other frame circuit breakers. Feeder switches can be CM1, HSM1, RMM1, SM1 and other plastic circuit breakers. Low voltage side cabinet type can be GGD fixed switch cabinet or other withdrawable switch cabinet.
High voltage side:
According to the requirements of users, the high voltage side can be equipped with pressurized air load switch, vacuum load switch, SF6 load switch, ZN21, VB5, VS1 or VD4 vacuum circuit breakers.High voltage side cabinet can be HXGN ring main unit, inflatable cabinet or other high voltage switch. cabinet.
Power transformer:
The power transformer capacity can be 30, 50, 63, 80, 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000kVA.Dry type transformer or oil - immersed transformer is optional. According to the design, one substation can install one or two transformers with different specifications.

Name | Unit | Data | ||||
Rated frequency | Hz | 50/60 | ||||
High voltage unit | Rated voltage | kV | 3 | 6 | 10 | 35 |
Maximum working voltage | kV | 3. 6 | 7. 2 | 12 | 40.5 | |
Power frequency withstand voltage to earth/interphase isolating distance | kV | 25/ 27 | 30/ 34 | 42/ 48 | 95/ 118 | |
Lightning impulse withstand voltage to earth/ interphase isolating distance | kV | 40/ 46 | 60/ 70 | 75/ 85 | 185/ 215 | |
Rated current | A | <=630 | ||||
Rated short-time withstand current | kA/ 2s (kA/ 4s) | 12. 5 ,16,20,25,31. 5 | ||||
Rated peak withstand current | kA | 31. 5 ,40,50,63,80 | ||||
\ | Rated voltage | V | 220 | 380 | 690 | |
Rated current of main circuit | A | <=3200 | ||||
Rated short-time withstand current | kA/ 1s | 15,30,50 | ||||
Rated peak withstand current | kA | 30,63,105 | ||||
Rated current of branch circuit | A | <=1600 | ||||
Reactive power compensation capacity | kvar | <=600 | ||||
Transformer unit | Rated capacity | kVA | <=2000 | |||
Impedance voltage | % | 4,4. 5 ,6 | ||||
Tap ranges | ±2X2. 5%,±5% | |||||
Connections | Y/ Yn0 ,D/ Yn11 |
Generally, transformer capacity below 315kVA is measured by low voltage, while capacity above 315kVA is measured by high voltage.